Infrastructure design

Network Rack Designer

Place equipment, check fit, power, and bonding, and generate an order list.

Rack Setup

Rack details, weight and cable entry

Use the smallest available side gap.

Rack depth settings

Exterior depth · 40″
Front rail to door / wall · 4″
Post spacing · 28″
Rear rail to door / wall · 5″
The shaded section runs between the front and rear mounting rails. Diagram is schematic.

Measure to the inside of each closed door.

Rear 0U channels

Measure from the rear rail. Enter a positive distance behind it or a negative distance toward the front.

Rack Layout

19 / 24U used on the front · 5U available · 0U reserved

Rack 01

24U · Floor cabinet · 4-post

1 circuit over limit · Check circuits

Intentional demo overlap. The rear cable manager at U6 overlaps the front storage server. Select Side view to see the overlap.

FRONT ELEVATION19″ RACK
0U
U1 at bottomDrag the grip to move. Hold the item and drag up or down to resize.
Rear left · Vertical rack bonding busbar (RBB) · Right in this viewFront right · Rack bonding strip (RBS)Unit Bonding Conductor (UBC)
Equipment Patch / fiber Power Bonding Auto blank Reserved Exception No wall circuit Single-fed On over-limit circuit
Rear free space 18U · Largest rear opening 6U
Fit checks
  • Conflict
    Storage server and Cable manager (U6) · Depth conflict. Chassis overlap by 5.5 in (33.5 in combined depth, 28 in between posts).
  • Verify
    Battery-backed vertical PDU · verify 0U clearance for rear cables and service access.
  • Verify
    Vertical rack bonding busbar (RBB) · verify 0U clearance for rear cables and service access.

Spare Space & Blanking Panels

5U available · largest opening 5U · 0U reserved

Optional settings · Automatic blanking off
Automatic panels are off.

Power & UPS

Wall circuits

Circuit A · 120 V AC · L5-20R · 20 A breaker / Circuit B · 120 V AC · L5-20R · 20 A breaker

This tool assumes there are two 20 A circuits available. Please customize this to your unique setting if different.

Outlet counter10 used26 free on PDUs / UPSs

Outlet and load reports

Filled symbols show assigned plugs. Outlined symbols show available outlets. Red symbols show plugs over capacity. Outlet positions are schematic.

Wall circuit · 120 V AC · L5-20R

Connected load
2,112.24 W
Est. circuit current
18.3 A120 V AC · Includes W converted using input PF
Breaker rating
20 A
Continuous planning limit
16 A

Critical warningEstimated current 18.3 A · 2.3 A over the continuous planning limit.115% of the continuous planning limit.

The demo load is intentionally high to show the continuous-limit and failover checks.

A/B failover · Normal 18.3 A. If Circuit B is lost, 21.5 A. See A/B details Over limit · 21.5 A on failover · 16 A planning limit

Planning scenario · Base 18.3 A · Adjusted 20.2 A · 100% diversity · 10% growth (over limit)

Try a planning scenario

Preview · Base 18.3 A · Adjusted 20.2 A (over limit)

Only on Circuit A · , , .

1 plug planned on this circuit · 1 of 2 wall outlets free

DevicePlugsInput WEst. input A
Front U1–U212,112.24 W18.3 AEstimated using input PF

Wall circuit · 120 V AC · L5-20R

Connected load
992.34 W
Est. circuit current
8.6 A120 V AC · Includes W converted using input PF
Breaker rating
20 A
Continuous planning limit
16 A

A/B failover · Normal 8.6 A. If Circuit A is lost, 14.4 A. See A/B details

Planning scenario · Use diversity and growth to preview an adjusted current.

Try a planning scenario

Preview · Base 8.6 A · Adjusted 8.6 A

Only on Circuit B · .

1 plug planned on this circuit · 1 of 2 wall outlets free

DevicePlugsInput WEst. input A
Front U3–U41992.34 W8.6 AEstimated using input PF

UPS · Front U1–U2

UPS plugs into Circuit A

Connected load
1,990 W
Est. UPS output current
17.8 A120 V AC · From entered amps or VA
UPS wall input estimate

2,112.24 W · 18.3 A

Line-mode efficiency (wall-circuit input) · 95.8% (interpolated).

1,990 W battery-backed output ÷ efficiency + 0 W AC-only pass-through + 35 W recharge. Input PF 0.96 applies to the converted and recharge load.

Battery-mode efficiency (runtime only) · 90% in the current runtime estimate. See runtime calculator

UPS exceeds a limit if Circuit B is lost. See UPS limits after transfer

Battery-backed

Assigned load · 1,990 W

5 plugs assigned · 3 available

DevicePlugsInput WEst. input A
Front U231420 W3.8 A
Front U7–U81350 W3.3 A
Front U9–U101620 W5.5 A
0U Rear right1600 W5.3 A
Front U1110 W0 A
Battery-backed vertical PDU · PDU summary
Plugs in PDU
1 / 8
PDU input watts
600 W
Est. PDU input amps
5.3 A
AC-only

Assigned load · 0 W

0 plugs assigned · 2 available

No devices connected.

UPS · Front U3–U4

UPS plugs into Circuit B

Connected load
970 W
Est. UPS output current
10.2 A120 V AC · From entered amps or VA
UPS wall input estimate

992.34 W · 8.6 A

Line-mode efficiency (wall-circuit input) · 94%.

350 W battery-backed output ÷ efficiency + 620 W AC-only pass-through + 0 W recharge. Input PF 0.96 applies to the converted and recharge load.

Battery-mode efficiency (runtime only) · Set in the UPS runtime calculator. See runtime calculator

UPS exceeds a limit if Circuit A is lost. See UPS limits after transfer

Battery-backed

Assigned load · 350 W

2 plugs assigned · 4 available

DevicePlugsInput WEst. input A
Front U9–U1010 W0 A
Front U111350 W4.8 A
AC-only

Assigned load · 620 W

1 plug assigned · 3 available

DevicePlugsInput WEst. input A
Rear U231620 W5.4 A
AC-only PDU · PDU summary
Plugs in PDU
1 / 8
PDU input watts
620 W
Est. PDU input amps
5.4 A

PDU · Rear U23

PDU plugs into Rackmount UPS 2 · AC-only · Front U3–U4

Connected equipment load
620 W
Est. PDU input current
5.4 A120 V AC · From entered amps or VA
PDU input limit
15 A
UPS outlet limit
15 A

1 plug assigned · 7 available

DevicePlugsInput WEst. input A
Front U191620 W5.4 A

PDU · 0U Rear right

PDU plugs into Rackmount UPS 1 · Battery-backed · Front U1–U2

Connected equipment load
600 W
Est. PDU input current
5.3 A120 V AC · From entered amps or VA
PDU input limit
15 A
UPS outlet limit
15 A

1 plug assigned · 7 available

DevicePlugsInput WEst. input A
Front U5–U61600 W5.3 A
Rack-room heat estimate8,085 BTU/hr2,369.58 W local heat

Outlets are counted at the source each device plugs into. Add each PDU or UPS as its own equipment row to assign loads to it. Upstream watt and VA totals count each load once. Watts and VA for PDUs and UPSs show the load on their outlets. Current is tracked at the wall circuit, PDU input, and UPS output. Current uses entered input amps or VA when available. Watts-only entries use the specified input power factor or the 0.90 planning assumption.

Power sourceLevelOutletsEntered wattsEntered VAEst. currentSource limits
Wall circuit20 A breaker · 120 V ACNEMA L5-20R
1 / 2 used1 free
2,112.24 WN/A18.3 A120 V AC · Includes watts converted using input PF2.3 A over continuous planning limit20 A breaker
Wall circuit20 A breaker · 120 V ACNEMA L5-20R
1 / 2 used1 free
992.34 WN/A8.6 A120 V AC · Includes watts converted using input PF20 A breaker
UPS outputFed by Circuit A
Battery-backed · 5 / 8 used3 free
AC-only · 0 / 2 used2 free
1,990 WBattery-backed · 1,990 WAC-only · 0 W2,130 VA17.8 A120 V AC · From amps or VA2,160 W / 2,400 VA
PDU inputFed by Rackmount UPS 2 · AC-onlyVerify UPS outlet and outlet-group limits.
1 / 8 used7 free
620 W650 VA5.4 A120 V AC · From amps or VA9.58 A estimated remaining15 A / 1,800 W
PDU inputFed by Rackmount UPS 1 · Battery-backedVerify UPS outlet and outlet-group limits.
1 / 8 used7 free
600 W630 VA5.3 A120 V AC · From amps or VA9.75 A estimated remaining15 A / 1,800 W
UPS outputFed by Circuit B
Battery-backed · 2 / 6 used4 free
AC-only · 1 / 4 used3 free
970 WBattery-backed · 350 WAC-only · 620 W1,225 VA10.2 A120 V AC · From amps or VA1,440 W / 1,500 VA
Circuit planning and A/B failover

Current uses entered RMS amps, then VA, then watts and input power factor (0.90 when unspecified). The continuous-load check uses 125% of continuous amps plus noncontinuous amps for standard-rated assemblies. Warning levels are 70% and 90% of the applicable limit. Continuous-load guidance

CircuitBase loadCurrentDiversity and growth scenario
Circuit A2,112.24 W18.3 A2,323.47 W · 20.2 A100% diversity · 10% growthOver the continuous planning limit
Circuit B992.34 W8.6 ASet in wall circuit settings

A/B failover

Each scenario models sustained loss of one wall circuit after UPS batteries run down. Single-fed equipment on that circuit loses power.

40% shortcut example: Two equal 20 A feeds each carry 8 A normally. If all load transfers, the survivor carries 16 A. The results below use the assigned transfer paths and entered limits.

Circuit A lost

Load transfers: Analytics server.

Power lost: 48-port PoE switch, Video recording server, Storage server.

Surviving circuitNormalAfter transferContinuous limit
Circuit B8.6 A14.4 A16 A

Rackmount UPS 2 · 1,590 W exceeds 1,440 W rating.

Rackmount UPS 2 · 1,885 VA exceeds 1,500 VA rating.

Circuit B lost

Load transfers: Management server.

Power lost: 24-port PoE switch.

Surviving circuitNormalAfter transferContinuous limit
Circuit A18.3 A21.5 A16 A Over limit · 21.5 A on failover · 16 A planning limit

Rackmount UPS 1 · 2,340 W exceeds 2,160 W rating.

Rackmount UPS 1 · 2,705 VA exceeds 2,400 VA rating.

UPS runtime calculator

Size the UPS from its backed-up load and compare battery energy requirements for different runtimes.

The demo starts with example battery energy and efficiency values. Use your UPS and battery specifications for an actual design.

UPS sizing and runtime targets

Backed-up load
1,990 W / 2,130 VAUses entered amps or VA
Minimum UPS rating with 20% headroom
2,556 VA / 2,388 W
Suggested UPS size class
3,000 VA
Target runtimeEnergy at UPS outputUsable battery energy at 90% efficiency
5 min166 Wh AC185 Wh DC
15 min498 Wh AC553 Wh DC
30 min995 Wh AC1,106 Wh DC
60 min1,990 Wh AC2,212 Wh DC

Runtime targets use 1,990 W. Check the selected UPS’s W and VA ratings and input requirements. UPS sizing guidance

Use identical packs approved for the UPS. For VRLA, use short-duration discharge data at the planned load.

Use manufacturer runtime data

Enter two points from the same UPS runtime curve for the selected number of battery packs. Pick points that bracket your load. Runtime is interpolated between them.

About 29 minEstimated runtime at 1,990 W with 1 external pack
Battery configurationTotal runtimeAdded vs. UPS only
UPS onlyAbout 15 min—
1 external packAbout 29 minAbout 15 min

Runtime in minutes = total usable DC Wh × efficiency as a decimal ÷ load W × 60.

Preview on UPS

Circuit B → Rackmount UPS 2 battery-backed outlets → AC-only PDU → Equipment

Load pointWattsVAEst. currentOutletsEntered limits
Rackmount UPS 2 output970 W1,225 VA10.2 A
Battery-backed · 3 / 6 used3 free
AC-only · 0 / 4 used4 free
1,440 W / 1,500 VA
Circuit B input1,031.91 WN/A9 A
1 / 2 used1 free
20 A breaker

PDU input current: 5.4 A.

Equipment backed up by Rackmount UPS 2

DeviceFed byQtyEntered input WEst. input A
Rackmount UPS 1 · Battery-backed1620 W0 A
AC-only PDU1620 W5.4 A
Rackmount UPS 2 · Battery-backed1350 W4.8 A

Current uses entered amps or VA where available. Watts-only inputs use the equipment power factor or the 0.90 planning assumption. Set the UPS output voltage and verify the manufacturer’s runtime data at the planned load.

Entered UPS receptacle limit: 15 A. Check plug compatibility and the shared outlet-group limit.

Rack Bonding

Place hardware and record the bonding path.

Keep the bonding conductor as short and straight as practical. Avoid sharp bends.

Bonding checks
  • Verify
    48-port PoE switch · specify the unit bonding conductor (UBC) part number.
  • Verify
    24-port PoE switch · specify the unit bonding conductor (UBC) part number.
Conductor, lugs and installation notes

Rack reports

Review fit, source loads, and the materials to order.

Upstream input load 3,104.58 W

Equipment weight 377 lb512 lb loaded

PositionEquipmentQtyU per itemTotal UDepthInput WWeightPower sourceBonding method
Front U2411U1U4 in03 lbNo power requiredUnit Bonding Conductor (UBC)Vertical rack bonding busbar (RBB)
Front U23In all situations, grounding practices must comply with Section 250 of the National Electric Code (NEC) requirements or local laws and regulations. A 6 AWG grounding wire is preferred from the chassis to the rack ground or directly to the common bonding network (CBN). The equipment rack should also be connected to the CBN with a 6 AWG grounding wire. Grounding lugs must be installed on the location marked on the chassis only.11U1U18 in42018 lbRackmount UPS 1 · Battery-backedUnit Bonding Conductor (UBC)Vertical rack bonding busbar (RBB)
Front U2211U1U2 in02 lbNo power requiredNo separate bond specified
Front U2111U1U4 in03 lbNo power requiredUnit Bonding Conductor (UBC)Vertical rack bonding busbar (RBB)
Front U2011U1U6 in03 lbNo power requiredNo separate bond specified
Front U19In all situations, grounding practices must comply with Section 250 of the National Electric Code (NEC) requirements or local laws and regulations. A 6 AWG grounding wire is preferred from the chassis to the rack ground or directly to the common bonding network (CBN). The equipment rack should also be connected to the CBN with a 6 AWG grounding wire. Grounding lugs must be installed on the location marked on the chassis only.11U1U18 in62018 lbAC-only PDUUnit Bonding Conductor (UBC)Vertical rack bonding busbar (RBB)
Front U14–U1815U5U—01 lbNo power requiredNo separate bond specified
Front U12–U13Verify the mounting hardware and any bonding required for the selected shelf.12U2U10 in08 lbNo power requiredNo separate bond specified
Front U11Demo assumes protective earth through the power cord. Check the model instructions and project requirements for any separate chassis bond.11U1U30 in35055 lbRackmount UPS 2 · Battery-backedNo separate bond specified
Front U9–U10Demo assumes a manufacturer-approved chassis bonding point. Verify the terminal and hardware for the selected model.12U2U30 in62055 lbRackmount UPS 1 · Battery-backedUnit Bonding Conductor (UBC)Vertical rack bonding busbar (RBB)
Front U7–U8Demo assumes protective earth through the power cord. Check the model instructions and project requirements for any separate chassis bond.12U2U27 in35038 lbRackmount UPS 1 · Battery-backedNo separate bond specified
Front U5–U6Demo assumes protective earth through the power cord. Check the model instructions and project requirements for any separate chassis bond.12U2U30 in60055 lbBattery-backed vertical PDUNo separate bond specified
Front U3–U4Demo assumes a manufacturer-approved chassis bonding point. Verify the terminal and hardware for the selected model.12U2U23 in—43 lbCircuit BUnit Bonding Conductor (UBC)Vertical rack bonding busbar (RBB)
Front U1–U2Demo assumes a manufacturer-approved chassis bonding point. Verify the terminal and hardware for the selected model.12U2U23 in—54 lbCircuit AUnit Bonding Conductor (UBC)Vertical rack bonding busbar (RBB)
Rear U2411U1U6 in04 lbNo power requiredUnit Bonding Conductor (UBC)Vertical rack bonding busbar (RBB)
Rear U2311U1U3.5 in02 lbRackmount UPS 2 · AC-onlyNo separate bond specified
Rear U2111U1U1 in02 lbNo power requiredNo separate bond specified
Rear U1811U1U3.5 in02 lbNo power requiredNo separate bond specified
Rear U1311U1U3.5 in02 lbNo power requiredNo separate bond specified
Rear U611U1U3.5 in02 lbNo power requiredNo separate bond specified
Vertical 0U · Rear right10U0U—07 lbRackmount UPS 1 · Battery-backedNo separate bond specified

New rack

Creating a new rack replaces the current working rack.

Start with a cabinet size

Presets use 19-inch mounting width. Post spacing values are for demonstration only. In Rack setup, confirm the post count and enter your actual rail spacing, clearances, and load rating.